HomeMy WebLinkAbout2198 Fire Safety Requirements for Transient AccommodationsORDINANCE NO.
AN ORDINANCE ESTABLISHING FIRE SAFETY REQUIRE-
MENTS FOR TRANSIENT ACCOMMODATIONS CONSISTING
OF LESS THAN THREE UNITS WITHIN THE CITY; SET-
TING FORTH REGULATIONS AND INSPECT REQUIREMENTS;
PROVIDING FOR ENFORCEMENT; AND ESTABLISHING AN
EFFECTIVE DATE
The City Council of the City of Port Townsend, in regular
session assembled, does ordain as follows:
Section 1. Purpose. The purpose of this ordinance is to
establish minimum fire and life safety requirements necessary
for obtaining certification for buildings, or portions thereof,
either licensed or applying for license as transient accommoda-
tions in the City of Port Townsend.
Section 2. Definitions.
A. Transient accommodation(s) shall mean any
facility such as a hotel, motel, bed and breakfast inn, tourist
home, resort, residence, condominium or any other facility or
place which offers less than three (3) lodging units to travel-
ers or transient guests for compensation for periods of less
than one (1) month.
B. Automatic fire alarm system is a system
which automatically detects a fire condition and actuates a fire
alarm system.
Section 3. Application and Scope. The provisions of these
regulations shall apply to existing conditions as well as to
conditions arising after the adoption thereof.
Section 4. Inspections and Approval.
A. Upon receipt by the City of an application
for a license or conditional use permit for any transient accom-
modation, the City of Port Townsend Fire Department shall pro- ~
vide inspection for compliance with these regulations relating
to fire and life safety. Upon completion of the inspection, and
if the building is found to be in substantial compliance with
these regulations, a notice of conditional approval shall be
filed with the City Building Office, and with the application
for license or conditional use permit.
B. The Fire Department may deny approval of
ORDINANCE - 1 -
buildings which are not provided with adequate egress or fire
warning system; or by reason of fire hazard, dilapidation, inade-
quate maintenance or a condition or conditions representing a
clear and present danger to transient persons subject to occu-
pancy of the building.
Section 5. Historic Buildings. Repairs, alterations and
additions necessary for the preservation, rehabilitation or con-
tinued use of a building or structure may be made without con-
formance to all the requirements of this code when authorized by
the Fire Inspector provided that:
1. The building or structure has been desig-
nated by official action of the legally constituted authority of
this jursidiction as having special historical or architectural
significance;
2. Any unsafe conditions as described in this
code are corrected; and
3. The restored building or structure will be
no more hazardous based on life safety, fire safety and sanita-
tion than the existing building.
Section 6. Hazardous Areas. Every room containing a boiler
or central heating plant, laundry, parking garage, storage room,
commercial kitchen~ mechanical room, electrical utility room,
maintenance shop and other spaces within the building deemed by
the Fire Department to present a hazard to the safety of the
guests shall be separated from the guest areas and the exits and
exit corridors by at least one-hour fire resistive construction.
Communicating openings shall be protected by approved self-
closing fire doors.
Section 7. Fire Alarm System.
A. An approved automatic fire alarm system
shall be installed in transient accommodations where the guest
room(s) exit into common interior corridors, hallways or passage-
ways; or the building is two stories or more in height. The
fire alarm system shall include provisions for smoke detection
and manual operation in the interior and automatic detection in
storage rooms, laundry rooms, utility rooms, furnace rooms,
janitorial-maintenance rooms, and toilets opening on exit cor-
ridors. Fire alarm system plans and equipment and specifica-
tions shall be submitted for review and acceptance before the
system is installed.
B. Installation, inspection and maintenance of
fire alarm systems shall be in accordance with these regulations
and Chapter 212-14 WAC.
ORDINANCE 2 -
C. Signaling devices shall be located and in-
stalled to ensure the signal audibility level is not less than
sixty (60) decibels at the bed pillow in the most remote guest
rooms, with all intervening doors in the closed position.
D. An alarm-sending station shall be provided
at the desk or other location under continuous supezvision by em-
ployees. Additional sending stations shall be located at or near
each required exit from each floor.
E. Where transient accommodations are equipped
with automatic sprinkler systems, an electrical interconnection
shall be provided between the sprinkler system and the fire
alarm system, whereby activation of the sprinkler system will re-
suit in an alarm signal.
F. The fire alarm system shall be under the
supervision of a responsible person, who shall cause proper
tests and inspections to be made at least once each month.
G. Every guest room in a transient accommoda-
tion used for sleeping purposes shall be provided with at least
one (1) Underwriters Laboratories (UL) listed smoke detector.
This requirement shall apply retroactively to transient accommo-
dations previously inspected and approved as well as to transient
accommodations inspected after the effective date of these regu-
lations. In new construction, required smoke detectors shall re-
ceive their primary power from the building wiring when such wir-
ing is served from a commercial source. Wiring shall be permanent
and without a disconnecting switch other than those required for
overcurrent protection. Smoke detectors may be battery-operated
when installed in existing building~ or buildings without commer-
cial power. Smoke detectors shall be installed and maintained in
accordance with the manufacturers'/instructions and these regula-
tions.
Section 8. Exit Corridors, Guest Room Doors. When used in
these regulations, the term "corridor" shall include exterior
exit balconies and any covered or enclosed exit passageway in-
cluding walkways and tunnels. Corridors serving as the required
exit for an occupant load of ten (10) or more shall meet the fol-
lowing requirements:
1. Exit corridors shall not be interrupted by
intervening rooms, except that foyers, lobbies or reception rooms
constructed as required for corridors shall not be construed as
intervening rooms.
2. Corridors shall be not less than thirty-six
(36) inches in width. The required width of corridors shall be
ORDINANCE - 3 -
unobstructed except for handrails and doors swinging to the fully
opened position.
3. Corridor walls, except exterior sides of ex-
terior exit balconies, should be not less than one-hour fire re-
sistive construction, and ceilings should be not less than that
required for one-hour fire resistive floor or roof system.
4. Corridors and exterior exit balconies should
have clear height of seven (7) feet measured from the lowest pro-
jection from the ceiling.
5. When more than one (1) exit is required,
the exits shall be so arranged that it is possible to go in either
direction from any point in a corridor to a separate exit, except
for dead ends not exceeding twenty (20) feet in length.
6. ~ere corridor walls are required to be of
one-hour fire resistive construction, every door opening shall be
protected with a tight-fitting smoke and draft control door assem-
bly having a fire protection rating of not less than twenty (20)
minutes. Doors shall be maintained self-closing or may be auto-
matic closing by actuation of a smoke detector electrically inter-
connected to an approved fire alarm system.
a. Exception: Protection of openings in the
interior walls of exterior exit balconies is not required.
b. Exception: Previously approved one and
three-quarter (1-3/4) and one and three-eighth' (1-3/8) inch solid
wood core doors, and doors upgraded to meet minimum requirements
for fire resistance by the installation of fire resistive materials
securely fastened to the door rails.
7. Where corridor walls are required to be of
one-half-hour fire resistive construction, interior openings for
other than doors or ducts shall be protected by fixed approved
one-fourth inch thick wired glass installed in steel frames. The
total area of all openings, other than doors, in any portion of an
interior corridor shall not exceed twenty-five percent (25%) of
the area of the corridor wall of the room which it is separating
from the corridor, except that protection of openings in the in-
walls of exterior exit balconies 15 not required.
8. Corridor walls not required to be one-hour
fire resistive construction may be surfaced with wood lath and
plaster in good condition or one-half inch gypsum wallboard. Pene-
etrations shall be repaired using materials commensurate with the
surrounding wall construction. Transoms shall be fixed in the
closed position, and the opening covered with five-eighths inch
ORDINANCE - 4 -
gypsum wallboard securely fastened in the corridor and room side
of the opening.
Section 9. Number of Exits, Arrangements, Exit Doors.
A. Occupied floors above the first story having
an occupant load of ten (10) or more, floors above the second
story, and basements shall have not less than two (2) separate
exits from the floor or basement, with the following exceptions:
1. Floors and basements used exclusively
for service of the building may be served by one exit.
2. Storage rooms, laundry rooms and main-
tenance offices not exceeding three hundred (300) square feet in
floor area may be served by one exit.
3. Previously approved fire escapes may
serve one required exit if well maintained and access thereto is
not obstructed.
B. If only two exits are required, they shall
be placed a distance apart equal to not less than one-half the
length of the maximum overall diagonal dimension of the building
or area to be served measured in a straight line between exits.
When three or more exits are required, they shall be arranged a
reasonable distance apart so that if one becomes blocked others
will be available.
C. When the occupant load is ten (10) or more
above the first story, exterior exit balconies shall be provided
with not less than two (2) remote stairways to ground level.
Dead ends shall not exceed twenty (20) feet in depth.
D. Every sleeping room below the fourth story
shall have at least one (1) operable window or exterior door ap-
proved for emergency escape or rescue. The units shall be oper-
able from the inside to provide a full clear opening without the
use of separate tools. All escape or rescue windows from sleep-
ing rooms shall have a minimum net clear opening of five and seven-
tenths (5.7) square feet. The minimum net clear opening height
dimension shall be twenty-four (24) inches. The minimum net clear
opening width dimension shall be twenty (20) inches. Where win-
dows are provided as a means of escape or rescue, they shall have
a finished sill height not more than forty-four (44) inches above
the floor.
Section 10. Access to Exits. Ail exits shall be accessible
from public areas or corridors without having to pass through in-
tervening rooms. In other than lodging houses, exits shall not
pass through kitchens, storerooms, restrooms, closets or spaces
used for similar purposes. Foyers, lobbies and reception rooms
approved as corridors shall not be construed as intervening rooms.
ORDINANCE - 5 -
Section 11. Exit Doors.
A. Exit doors shall be openable from the inside
without the use of a key or any special knowledge or effort, ex-
cept that exit doors from guest rooms of Group R, Division 1, and
Group R, Division 3, occupancies having an occupant load of ten
(10) or less may be provided with a night latch, dead bolt or se-
curity chain, provided such devices are openable from the inside
without the use of a key or tool and mounted at a height not to
exceed forty-eight (48) inches above the finished floor.
B. Exit doors should swing in the direction of
exit travel. Except for approved power-operated doors metting re-
quirements of Uniform Building Code standards, revolving, sliding
and overhead doors shall not be used as required exits.
Section 12. Exit Signs.
A. Exit signs shall be installed, when required,
at exit doorways and where otherwise necessary to clearly indicate
the direction of egress.
B. The color and design of lettering, arrows
and other symbols on exit signs shall be in high contrast with
their background. Words on the sign shall be in block letters six
(6) inches in height with a stroke of not less than three-fourths
(3/4) inch.
C. Signs shall be internally or externally il-
luminated by two (2) electric lamps or shall be of an approved
self-luminous type. When the luminance on the face of an exit
sign is from an external source, it shall have an intensity of not
less than five (5.0) footcandles from either lamp. Internally il-
luminated signs shall provide equivalent luminance.
D. Separate branch circuits are required for
exit illumination. Current supply to one of the lamps for exit
signs shall be from a circuit having outlets only for other exit
signs or exit illumination. Power to the other lamp shall be from
a separate circuit that may supply other outlets.
E. When separate sources of power are required
for exit illumination, power to one of the lamps for exit signs
shall be from storage batteries or an on-site generator set, and
the system shall be installed in accordance with the State of
Washington electrical code requirements.
Section 13. Corridor Lighting, Exit Illumination.
A. Except within guest rooms and sleeping rooms,
ORDINANCE
- 6
exits shall be illuminated at any time the building is occupied
with light having intensity of not less than one (1) footcandle at
floor level.
B. The power supply for exit illumination shall
be provided by two (2) separate branch circuits of the normal
premises wiring system, unless an emergency system is installed.
One of the required circuits shall supply only fixtures used for
exit illumination or exit signs; the other circuit may supply to
other outlets.
C. The power supply for exit illumination shall
normally be provided by the premises wiring system. In the event
of its failure, illumination shall be automatically provided from
an emergency system where the occupant load served by an interior
exit corridor system exceeds one hundred (100).
D. Emergency systems shall be supplied from
storage batteries or an on-site generator set, and the system
shall be installed in accordance with the requirements of the
State of Washington electrical code requirements.
Section 14. Fire Extinguishers.
A. At least one UL-listed 2A-10BC-rated fire
extinguisher shall be provided in the corridor of each guest-
occupied floor. Additional extinguishers shall be provided as re-
quired, to ensure that one is within twenty-five (25) feet of each
guest room door.
B. In buildings not having public corridors~ an
extinguisher shall be provided at a convenient location near the
registration desk in a plainly marked enclosure accessible at all
times to guests.
C. Additional extinguishers of a size and type
commensurate with the hazard presented shall be provided as re-
quired in other areas in which a fire would affect guest safety.
Section 15. Obstructions. Furniture, appliances or similar
objects shall not be placed in corridors, passageways or stair-
ways, or in such locations which would result in obstructing the
means of egress. Exits, exit signs, fire alarms and fire ex-
tinguishers shall be visible and not obstructed by curtains or
other decorative materials or fixtures.
Section 16. Control of Hazardous Conditions and Practices.
A. "NO SMOKING" signs shall be posted in rooms
or areas where the fire inspector determines smoking to be hazard-
ORDINANCE - 7 -
ous. Where smoking is permitted, suitable ashtrays or receptacles
shall be provided to deposit used smoking materials. When directed
to do so, the licensee or owner shall obtain and install NO SMOKING
signs at the locations specified by the City fire inspector.
B. Unvented fuel-burning room heaters shall not
be installed, used, maintained or permitted to exit in a transient
accommodation or lodging house subject to compliance with these
regulations. Use of portable electric space heaters or hot plates
in guest rooms, without prior written approval from the fire in-
spector, is prohibited.
C. Flammable liquids shall be stored in flamma-
ble liquid storage cabinets meeting the design and construction re-
quirements set forth in the Uniform Fire Code.
De
permanent writing.
Extension cords shall not be used in lieu of
E. Storage of combustible materials in furnace
rooms, boiler rooms, mechanical or utility rooms is prohibited.
F. Self-closing doors shall be maintained in the
closed position during occupancy hours, unless they are held open
on approved door holders electrically interconnected to the fire
alarm system. Installation of kick-down door stops or use of
wedges on fire doors is prohibited.
G. Electric baseboard heaters shall be fre-
quently cleaned as required to preclude accumulation of dust, lint
and debris. Combustible materials shall not be pi'aced or installed
within eighteen (18) inches of electric baseboard heaters.
H. Fireplaces shall not be used without a serv-
iceable fireplace screen installed in the fireplace opening.
I. The use of other solid fueled heating appli-
ances shall be subject to certification by the City fire inspector.
Section 17. Maintenance. Fire protection systems, equipment
and devices shall be maintained in accordance with these regula-
tions and Chapter 212-14 WAC.
A. Sprinkler systems, standpipe systems, fire
alarm systems, automatic fire detection systems, engineered or pre-
engineered fixed fire-extinguishing systems, portable fire ex-
tinguishers, exit lighting, fire doors, fire door hardware, closing
mechanisms and any other fire protection system or device required
by these regulations shall be maintained in operative condition at
all times.
ORDINANCE 8 -
B. At annual intervals, every fire protection
system and appliance shall undergo certification testing and in-
spection. Certification testing and inspection shall be accom-
plished by a person specializing in the fire protection system or
appliance being tested and inspected. The person performing the
certification testing and inspection shall possess the license or
credentials required by Washington State law. Results of certifi-
cation inspection and testing shall be verified. With respect to
portable fire extinguishers, maintenance is a "thorough check" of
the extinguisher. It is intended to give maximum assurance that
the extinguisher will operate effectively and safely. It includes
a thorough examination and any necessary repair or replacement.
It will normally reveal the need for hydrostatic testing.
C. Visual inspections and tests of fire protec-
tion systems and appliances, within the capability of the licensee
or owner, shall be performed in accordance with manufacturers in-
structions or NFPA standards. Records of licensee or owner testing
shall be maintained, and the subject system or appliance shall be
tagged with the date of service and signature.
D. Wall and ceiling penetrations shall be re-
paired with materials commensurate with the surrounding wall or
ceiling construction.
E. Outside fire escapes sarving as required
exits shall be maintained in good repair. Fire escapes detected
with rusted, twisted or broken components shall be required to
undergo structural and load testing as may be necessary to verify
their serviceability.
F. One or more fire watchmen shall be required
at any time a fire alarm system, automatic fire detection system
or automatic sprinkler system is impaired or inoperative. Fire
watchment shall be obtained from professional security firms or
may be fire service personnel. The establishment may utilize
their own employees, provided they are full-time security staff
employees with no other duties during their period of employment
as fire watchmen. Fire watchmen shall perform fire surveillance
patrols throughout the affected portions of the building between
the hours of four o'clock (4:00) p.m. through eight o'clock (8:00)
a.m. Fire surveillance patrols shall include, but not necessarily
be limited to, the following actions:
1. Patrolling corridors, stairways and
passageways, observing for smoke or any suspicious smoke odors;
2. Ensuring that corridors, stairways and
passageways are free of obstructions;
ORDINANCE - 9 -
3. Ensuring that fire doors are maintained
in the closed position;
4. Ensuring that any firefighting appliances
are at their proper location;
5. Monitoring gatherings of persons in
assembly areas to preclude overcrowding; and
6. Maintaining a record of surveillance
patrols.
Section 18.
Emergency Procedures Plan.
A. Each licensed transient accommodation shall
develop and maintain a written fire emergency plan, specifying
actions to be taken by the staff in the event of a fire emergency.
The procedures shall include:
1. The actions to be taken by the staff
upon being notified of a fire;
2. The actions to be taken for summoning
the Fire Department;
3. The actions to be taken for assisting
guests or others endangered by fire; and
4. The actions reqUired for guest safety
as directed by the Fire Department or a procedure for evacuating
the building.
B. The licensee or facility manager is respon-
sible for assuring the staff is familiar with their duties as de-
fined in the emergency plan. Training classes, covering each
element of the emergency plan, shall be conducted at the time of
employment and at annual intervals thereafter. An employee
training record, indicating the date of training and names of em-
ployees receiving training, shall be maintained.
C. Transient accommodations two (2) stories or
more in height, where exit travel is through interior corridors,
shall develop and post a fire safety information placard. The
placard shall contain information intended to enhance the per-
sonal safety of the guest during a fire incident. The placard
shall be fabricated from a durable material and securely fastened
to the room side of each guest room at approximately eye level.
The placard shall include, but not necessarily be limited to, the
following information:
1. The routes to primary and alternative
exit doors or exit stairways;
ORDINANCE - 10 -
2. Location of manual fire alarm devices;
3. Fire reporting telephone number;
4. Type of fire alarm signaling device,
such as bell, horn, buzzer, chime, electronic tone device and/or
voice speaker~
5. List of actions the guest should take
for personal safety during a fire incident, actions to take prior
to leaving the guest room and actions when confined to the guest
room; and
6. Information for fire reporting.
Section 19. Enforcement. An annual inspection shall be
provided by the Fire Department to ascertain continued compliance
with the regulations contained herein. Non-complance orders will
be provided the owner and/or manager of the transient accommoda-
tion citing deficiencies in writing, together with the remedy re-
quired and the time frame for compliance. The Fire Department
shall cause any unfulfilled non-compliance inspection orders to
be forwarded to the Planning and Building Department for action
under license or conditional use recision or denial procedures.
Section 20. Severability. If any provision of these regu-
lations or their application to any person is held invalid, the
remainder of the regulations or the application of the provision
to other persons or circumstances is not affected.
Section 21. Effective Date. This ordinance shall take
effect upon its passage, approval and publication in the form and
manner provided by law.
Read for the first, second and third times, passed by the
City Council for the City of Port Townsend and signed and ap-
proved by the Mayor this ~ day of ~ , 1990.
Attest:
David A Grove, City Clerk
ORDINANCE
- 11 -
Appro 'd as to form:
Kei-fil~ C. Harper, C±ty Atto y
Passed by City Council:
Signed by Mayor:
Published:
Effective date:
1990
1990
1990
1990
ORDINANCE
- 12 -