HomeMy WebLinkAboutBLD02-230
Watemwn & ICaiz Building
181 Quincy Street Suite 301
Port Townsend, WA 98368
Phone (360) 379-3208 Fax (360) 385-7675
CITY OF PORT TOWNSEND
PERMIT & INSPECTION RECORD
THIS CARD MUST BE POSTED AT CONSTRUCTION SITE
CALL 385-2626 FOR INSPECTION
Permit Number: BLD02-230 Issued: 11/12/02
lob Address: 210 Battery Way, Fort Worden State Park Zoning: P/OS
Nature of Work: Install Automatic Fire Sprinkler System
Use of Building: Multi-Purpose Dinin Fg acility
Owner: State of Washington. Pazks and Recreation Contractor: Foxfire Prevention Inc.
**(SEE ATTACHED FIRE DEPT. MEMO DATED 11/11/02)**
Site Inspections (Locates)
Cd. Fire Department Connection
^ Vault
^ Post Indicator Valve
Inspector !-/J~ Date
Construction Inspections
0 Piping, Bracing, Valve Installation
Ga Check valves
~ Drain and drip device between FDC and Check Valve
Q' Thrust Block Installations
L~ Approval for Cover (except joints-prior to flow test)
Inspector ~ Date
Page 1 of 2
Permi[ ABLD02-230
TOSpCCtl0I1s 8t TeSfS
C?~ Public Works Department Inspection Approval (double check detector assembly
prior to installation)
/n3pectOr f /d1 Date
~~
~~
Hydrostatic Test (2 hour, Z00 psi min.)
Pressurized Air Test (24-hour dry test to 40 psi)
Flush (with sieve)
Flow Test(s) (Water pressure gauge reading:~'f -Drop: -~~
Fire Alazm System Interne Test, Local Waterflow Alarm Req'd. (Tamper and
Flow)" Seconds
Pressure Reduction Valve required if static water supply pressure > 80 psi
Elevator hoistway provided with sprinkler head(s) at bottom (sidewall) and top
of elevator hoistway with appropriate shutoff valve in accessible location, not
more than six feet off floor level
@' Labeling (Control Valves, Drains, etc.)
GY Sprinkler Box Contents (wrench, heads, etc.)
fY Water Motor Alarm
p' Fire Department Connection -final fitting to meet City of Port Townsend's
Engineering Design Standard W-12 (attached)
~ Adequate heat provision for piping protection
lnspecfor /_~,rfU Dafe
^ Contractor's Material & Test Certificate filed:
~ As-built Plans (24 x 36" maximum format) provided on-site in a formal plans
box adjacent to sprinkler riser:
~ As-built Plans (24 x 36" maximum format) filed~ce~ ~ -~
Cd/ Fire Department Fi al nspection Approval
Ins Date
Page 2 of 2