HomeMy WebLinkAboutBLD03-297Waterman & Katz Building
I81 Quincy Street Sui[e 301
Port Townsend, WA 98368
(Phone) 379-3208 (Fax)365-7675
CITY OF PORT TOWNSEND
CONSTRUCTION PERMIT & INSPECTION RECORD
THIS CARD MUST BE POSTED AT CONSTRUCTION SITE
Call 385-2294 for Inspection
Permit Number: BLDO3-297 Issued: 01/09/04 Parcel Number: 97$ 300 003
Job Address: 1044 Lawrence Street Zoning: CC=HI Type: V_N Occupancy: A_3
Total Occupant Load: N/C Nature of Work: Install Tvne I Kitchen Hood with Make-ua
Air; Fire Suppression to be installed under Revision #1
Owner: Jav and Christine Payne dba Wild Cobo Contractor: Alaine Fire & Safety ALPINFS077RP
(360)379-1030
GENERAL CONDITIONS APPLY -SEE LAST PAGE
SEPARATE PERMITS REQUIRED:
Electrical -Contact Labor & Industries @ 360-417-2702
MECHANICAL -see attached duct wrap NER
Appliance/Exhaust Interlock
Exhaust Outlet Clearance - 2' above roof,• Y other
Type Ipuct Gage
Duct Joints/Seams -continuous liquid-tight weld -
Grease-Duct Supports - no penetration of duct walls
Duct Slope -'/<: IZ
Duct/Enclosure Separation - 3 "min.; 12" maz or per wrap
specs
Duct Enclosure/Shaft -duct wrap manufacturer's instructions
skald be on-site at time of Inspection
Cleanouts
Air Velocity
DucUCombustible Clearance -18 "; 3 "from non-combustibles
or per duct wrap specs
Hood Flashing -less than I2 "from ceiling or walls requires
flashing with 22 gage steel
Make-up Air
- 5 feet separation from exhaust
- Duct insulation R-3.3
Grease Filters
Canopy Hood -Installed per manufacturer's instructions
~.
Page 1 of 2
Building Permit #HLD03-297
FINAL
Fire Department Approval
Building
Make-up Air Vent and Exhaust Terminatian shalt be patnted to
match existing roof/building
GENERAL CONDITIONS
1. Contractors working on this project are required to have a Labor & Industries contractor's reeistration
number and a City business license. Failure to provide proof of this documentation prior to work may
result in job shut down while this is accomplished.
2. Temporary erosion and sediment control (TESC) measures shall be installed on-site and inspected prior
to beginning construction; call 385-2294. Measures shall include installation of silt fencing and graveled
construction entrance (see attached details). Adjacent rights-of--way shall be kept free of dirt debris. Soils
exposed during construction shall be temporarily stabilized with mulching, plastic sheeting, etc. Soils
shall be permanently stabilized with seeding, plantings, sodding, etc. once construction is complete.
Applicant is responsible for protection of adjacent properties.
3. All elements of engineering including nai-ing, holdowns, sheathing, and alternate braced wall panels
(ABWP) require inspection prior to cover.
4. -Owner or owner's agent shall review and oversee correction of any and all deficiencies noted by required
inspections.
5. Re-inspection is required after inspection report corrections are completed.
6. The Building Department is unable to pass final inspection on your project until Public Works
requirements have been completed and inspected. For Public Works inspection ca11 3 8 5-2 2 94. A
7. Final Inspections are required prior to occupancy; A Certificate of Occupancy is required fora non-
residential project.
8. All building permits expire if no progress has been made within six months, or if no inspections are done
by the Building Department within one year. Call for at least one inspection per year to keep your
building permit active.
9. Revisions require submittal & approval prior to making changes in the field. Contact the Building
Department @ 379-3208 prior to making changes to the approved plans.
10. POST THIS PERMIT ON-STYE WITH THE APPROVED PLANS.
•
Page 2 of 2
Waterman & Katz Building
181 Quincy Street Suite 301
Por[ Townsend, WA 98368
(Phone) 379-3208 (Fax) 385-7675
CITY OF PORT TOWNSEND
~,
•
CONSTRUCTION PERMIT & INSPECTION RECORD
THI5 CARD MUST BE POSTED AT CONSTRUCTION SITE
Ca113S5-2294 for Inspection
Permit Number: BI,D03-297R-2 Issued: 03/02/04 Parcel Number: 975 300 003
Job Address: 1044 Lawrence Street Zoning: C=III Type: V'N Occupancy: A_3
Total Occupant Load: N/C Nature of Work: Revision #2: drywall ceiline and inspect
duCYitlg•
Owner: Jav and Christine Payne dba Wild Coho Contractor: Owner
GENERAL CONDITIONS APPLY -SEE LAST PAGE
SEPARATE PERMITS REQUIRED:
Electrical -Contact Labor & Industries @ 360-417-2702
SEE ORIGINAL PERMIT FOR OTHER INSPECTIONS.
RF.OTTIRED TNSPECTIONS
APPROVED/DATE
DRYWALL
~
Ceiling '
/ ' ' ~
MECHANICAL
Ducting
Page 1 of 2
Building Permit /tBLD03.297
FINAL
Fire Department Approval
Building
Make-up Air Dent and E.zhaust Termination shall be painted to
match existing roof/building
GENERAL CONDITIONS
1. Contractors working on this project are required to have a Labor & Industries contractor's
registration number and a City business license. Failure to provide proof of this documentation
prior to work may result in job shut down while this is accomplished.
2. Temporary erosion and sediment control (TESC) measures shall be installed on-site and
inspected prior to beginning construction; ca11385-2294. Measures shall include installation of
silt fencing and graveled construction entrance (see attached details). Adjacent rights-of-way
shall be kept free of dirt debris. Soils exposed during construction shall be temporarily
stabilized with mulching, plastic sheeting, etc. Soils shall be permanently stabilized with seeding,
plantings, sodding, etc. once construction is complete. Applicant is responsible for protection of
adjacent properties.
3. All elements of engineering including nailing, holdowns, sheathing, and alternate braced wall
panels (ABWP) require inspection prior to cover.
4. Owner or owner's agent shall review and oversee correction of any and all deficiencies noted by
required inspections.
5. Re-inspection is required after inspection report corrections are completed.
6. The Building Department is unable to pass final inspection on your project until Public Works
requirements have been completed and inspected, For Public Works inspection call 385-2294. A
minimum of twenty-four hours notice is required. Public Works approval must be received
prior to scheduling the Building Department's final inspection.
7. Final Inspections are required prior to occupancy; A Certificate of Occupancy is required for a
non-residential project.
8. All building permits expire if no progress has been made within six months, or if no inspections
are done by the Building Departmeut within one year. Call for at least one inspection per year
to keep your building permit active.
9. Revisions require submittal & approval prior to making changes in the field. Contact the
Building Department @ 379-3208 prior to making changes to the approved plans.
10. POST THI5 PERMIT ON-SITE WITH THE APPROVED PLAN5.
Page 2 of 2
• THIS CARD MUST BE POSTED AT CONSTRUCTION SITE
CALL 385-2294 FOR INSPECTION
Permit Number: Ri.T)0'i-297R-1 Issued: Q]/09/04 Job Addtess: 1044 Tawrence Street- Wild ('nhn Rectaurant
Owner/Proprietor: ~ and (`hnct;nr Par Use of Building: Restaurant
Nature of Work: install Fire Snpnressinn System for ('ommercial Kitchen Hood
Contractor: Alnine Fire and Sag}v Rvsfama inc.
Conh~actor State License Number: AT.PINFR0T7RP F~ratinn 11/19!04
REQUIRED INSPECTIONS
•
^ UL 300 System orientation/installation in accordance with rnanufacturer's/[JL listing and City permit
^ Appliances properly covered with correct nozzle(s) (appliance manufacturer's listing)
^ Duct and plenum covered with correct nozzle(s)
^ Positioning of nozzles
^ Nozzle covers in place (where required)
^ Fusible links within rated temperature requirement
^ Hood/duct penetrations sealed with weldor UL listed device
^ Cylinder pressure gauge in proper range (if gauged)
^ Hydrostatic test date of cylinder current (CO2 cartridge exempt)
^ Inspect cylinder mount(s)
^ Check travel of cable(s)
^ Cable piping and conduit properly bracketed
^ Proper sepazation between fryer(s) and devices with surface flames
^ Proper surface to filters clearance
^ Exhaust fan in operating order
^ Filters in proper orientation
^ Fuel shut-off in "on" posifion for operation/test
^ -Fan warning sign on hood
^ Manual release and location proper
^ Personnel instructions in manual operation of system
^ Class K Fire extinguisher within 30 feet and tagged properly
^ 40-B:C Portable Fire Extinguisher available and tagged properly
^ Electrical panel properly labeled for shunt-trip function and manual reset, if applicable
^ Other:
Inspector:
Inspector:
Date:
Date:
^ Automatic Trip Test
^ Manual Trip Test
^ Fue]/Power disconnect for all hooded appliances/outlets (with manual reset)
^ Hood protection system monitored by premises automatic fire alarm system
^ Certification/service tag on system(s)
Inspector:
Inspector:
Date:
Date:
Page 1 of 1