PERMIT & INSPECTION RECORD
THIS CARD MUST BE POSTED AT CONSTRUCTION SITE
CALL 385-2626 FOR INSPECTION
Permit No: BLD98-00221 Issued: 031/19/99
Job Address: Building_#202 Fort Worden State Park Zoning: P/OS
Nature of Work: Install Fire Sprinkler System Use of Building: Meeting_/Conference
Owner: WA State Parks and Recreation Contractor: Grinnell Fire Protection Systems Co.
'x(SEE ATTACHED FIRE DEPT iV1EM0 DATED 1/11/99 & CONNECTIONBLOCKING/THRUST
BLOCK DETAILS)as
REOUIItED INSPECTIONS
Site Inspections (Locates)
^. Fire Department Connection
^ Vault
^ Post Indicator Valve
Inspecfor
Construction Inspections
Date
^ Piping, Bracing, Valve Installation
^ Check valves
^ Drain and drip device between FDC and Check Valve
^ Thrust Block Installations (Inspection by Water Distribution Division of Public
WOrkS) Inspector Date
^ ' Approval for Cover (except joints-prior to flow test)
Inspector Date
Inspections & Tests
^ Public Works (Water Distribution) Department Inspection Approval (double
detection check valve prior to installation)
Inspector Date
^ Hydrostatic Test (2 hour, 200 psi min.)
^ Pressurized Air Test (24-hour dry test to 40 psi)
^ Flush (with sieve)
^ Flow Test(s) (Water pressure gauge readings= Drop:~
^ Fire Alarm System Intertie Test, Local Waterflow Alarm Req'd. (Tamper and
Flow) _ Seconds
^ Sprinkler Head Installation
^ Labeling (Control Valves, Drains, etc.)
^ Sprinkler Box Contents (wrench, heads, etc.)
^ Water Motor Alarm
^ Fire Department Connection
^ Adequate heat provision for piping protection
/nspecfar ~ Date
^ Contractor's Material & Test Certificate filed:
^ As-built Plans (24 x 36" maximum format) provided on-site in a formal plans
box adjacent to sprinkler riser:
^ As-built Plans (24 x 36" maximum format) filed:
^ Fire Department Final Inspection Approval
Inspector. Dafe