Loading...
HomeMy WebLinkAboutBLD97-111CITY OF PORT TOWNSEND PERMIT & INSPECTION RECORD THIS CARD MUST BE POSTED AT CONSTRUCTION SITE CALL 385-2626 FOR INSPECTION Permit No: BLD97-00111 Issued: 07/17/97 Receipt No. Date Job Address: Victoria House/491 Discovery Road Use of Building: Assisted Living_ Nature of Work: Inst?ll Fire Sul2preccion y~em (,Kitchen Hoodl Zoning: R-11 Owner: Ac is ~ .wing .onc~gtc Contractor: Fire Control Inc. ***Sprinkler Protection Shall Be Provided for Enclosed Plenum Space Within the Hood Above Filters and Exhaust Ducts Serving the Hood per Attached Fire Dept. Memo*** ^. Fire Department Connection ^ Vault ^ Post Indicator Valve /nspector Date ^ Piping, Bracing, Valve Installation ^ Check valves ^ Drain and drip device between FDC and Check Valve ^ Thrust Block Installations ^ Approval for Cover (except joints-prior to flow test) /nspector • Date ^ Hydrostatic Test (2 hour, 200 psi min.) ^ Pressurized Air Test (24-hour dry test to 40 psi) ^ Flush (with sieve) ^ Flow Test(s) (Water pressure gauge reading:--Drop:_~ ^ Fire Alarm System Interne Test (Tamper and Flow) _ Seconds ^ Sprinkler head installation inspection ^ Labeling (Control Valves, Drains, etc.) ^ Sprinkler Box Contents (wrench, heads, etc.) ^ Water Motor Alarm ^ Fire Department Connection ^ Adequate heat provision for piping protection /nspector Dafe ^ Contractor's Material & Test Certificate filed: ^ As-built Plans filed: ^ Fire Department Final Inspection Approval ' Inspector Date i