HomeMy WebLinkAboutBLD97-106CITY OF PORT TOWNSEND t~~~ PERMIT & INSPECTION RECORD THIS CARD MUST BE POSTED AT CONSTRUCTION SITE CALL 385-2626 FOR INSPECTION Permit No: BLD97-00106 Issued: 08/28/97 Receipt No. Date Job Address: Victoria House/491 Discovery Road Use of Building: Assisted Living_ Nature of Work: Install Fire Srigprecsion yc em (~prin lercl Zoning: R-11 Owner: Assisted Living one ptc Contractor: Patriot Fire Protection ***See Attached Fire Dept. Memos dated 8/13/97 & 8/26/97*** ^. Fire Department Connection ^ Vault • ^ Post Indicator Valve Inspector Date ^ Piping, Bracing, Valve Installation ^ Check valves ^ Drain and drip device between FDC and Check Valve ^ Thrust Block Installations ^ Approval for Cover (except joints-prior to flow test) Inspector Date ^ ^ ^ ^ • ^ Hydrostatic Test (2 hour, 200 psi min.) Pressurized Air Test (24-hour dry test to 40 psi) Flush (with sieve) Flow Test(s) (Water pressure gauge reading:--Drop: Fire Alazm System Intertie Test (Tamper and Flow) _ Seconds Sprinkler head installation inspection ^ labeling (Control Valves, Drains, etc.) _ ^ Sprinkler Box Contents (wrench, heads, etc.) ~. ^ Water Motor Alarm ^ Fire Department Connection (see condition #8 of Fire Department memo dated 8/13/97, attached) ^ Adequate heat provision for piping protection Inspector Date ^ Contractor's Material & Test Certificate for Underground Piping filed: ^ Contractor's Material & Test Certificate for Aboveground Piping filed: ^ As-built Plans (24" x 36" format) filed with Fire Department: ^ As-built Plans (24" x 36" format) on-site in formal plans box: ^ Written Maintenance Specs provided to Owner (see condition #1 ^ Fire Department Final Inspection Approval Inspector Date •