HomeMy WebLinkAbout47th St. McNeil to San Juan Waterline Extensiona 9 W GENERAL NOTES: 1. ALL CONSTRUCTION SHALL COMPLY WITH THE CITY OF PORT TOWNSEND ENGINEERING DESIGN STANDARDS GRAPHIC SCALE w w a i inch — 50 & BENCH MARK 30 JOIN EX. 4" MAIN WITH 2" VALVE / 1 )) SQUARE NUT NO.25 CITY OF PORT TOWNSEND 49TH STREET & SAN JUAN STREET ELEV. 7.78 (NAVD 88) 20 10 11 12 PROFILE Hor 1 "= 30' Vert 1 "= 6' 13 30 10 GENERAL CONDITIONS: 1. A preconstruction meeting shall be held with the City prior to the start of construction. 2. All workmanship and materials shall be in accordance with the City of Port Townsend Standards, the current edition of the State of Washington Standard Specifications for Road, Bridge and Municipal Construction, and any project— specific provisions or conditions, and requirements. 3. Temporary erosion control measures are required and shall comply with the stormwater code, Chapter 5 of City EDS Standards and WSDOT /APWA Specification 1 -07.15 as follows: a) Erosion control plans shall be submitted to the City, approved by the City, and implemented by the contractor prior to distrubing any soil on the site. Submittal and approval of these plans shall precede any construction activity on the site. b) All permanent storage and retention /detention areas used as part of the temporary erosion control and water pollution /flood activities and conveyance systems shall be cleaned of all silts, sand, and other materials following completion of construction and the permanent facilities shall then be completed including permanent infiltration areas. 4. Horizontal and vertical controls /datum as adopted by the City shall be used, uless approved otherwise. 5. The contractor shall be fully responsible for the location and protection of all existing utilities. The contractor shall verify all utility locatons prior to construction by calling Underground Locate at 1- 800 - 424 -5555 a minimum of 48 hours prior to any excavation work. Y 6. All non — ferrous pipe and services shall be installed with continuous tracer tape installed 12" to 18" under the final ground surface. The marker tape shall be 4" wide minimum plastice non — biogradable, metal core or backing marked and color coded for the utility to be marked and which can be detected by a standard metal detector. Tape shall be Terra Tape "D" or approved equal. Inaddition to tracer tape, force mains and curved mains shall have a 14 gouge coated copper wire, wrapped around the pipe, brought up, coated shipped, and tied off at the valve stem or manhole ring. The tape and wire shall be furnished and installed by the contractor. 7. Temporary street patching may be allowed with the approval of the City Engineer. Temporary street patching shall be as described in Chapter 6 of the EDS. 8. The contractor shall provided a traffic control plan(s) for review and approval by the City Engineer in accordance with the Manual on Uniform Traffice Contral Devices (MUTCD). 9. The contractor shall have a copy of the approved plans and permits at the construction site at all times. 10. Special structures shall be installed per plans and manufacturers' recommendations. 11. All distrurbed areas shall receive temporary and permanent erosion control in the form of vegetation establishment such as grass seeding. A means shall be established to protect the permanent storm drain system prior to establishment of the permanent erosion control measures. These methods shall be included in the erosion and sediment control plans in accordance with Chapter 5 of these Standards. 12. Construction work hours shall be restricted to 7 AM to 6 PM, Monday through Friday, unless otherwise approved in writing. 13. The City Public Works Inspector shall be notified a minimum of 24 hours in advance of the need for an inspection. Every effort will be made to accommodate ;tame —day inspections if the City is notified before 8 AM. GENERAL CONDITIONS - - -- WATER 1. The City shall be given 72 hours EXIS ING GR UNp N cl the contractor shall make the necessary r rovisionons to thest the new line prior to connection to the existing system P OVI D 3' OVE 2. The existing valves shall only be operated by City employees during construction. 3. 211 WATER 7 Li- the R MAI of the day so that contaminates will not enter the lines. 4. All lines[ shall be chlorinated and tested in conformance with the standard specifications. Dechlorintation wll be done by City forces at contractor expense. 5. All water mains shall be staked for grades and alignment grade prior to starting construction. existi g 12 sewer END P INSTALL PE PLUG 10 11 12 PROFILE Hor 1 "= 30' Vert 1 "= 6' 13 30 10 GENERAL CONDITIONS: 1. A preconstruction meeting shall be held with the City prior to the start of construction. 2. All workmanship and materials shall be in accordance with the City of Port Townsend Standards, the current edition of the State of Washington Standard Specifications for Road, Bridge and Municipal Construction, and any project— specific provisions or conditions, and requirements. 3. Temporary erosion control measures are required and shall comply with the stormwater code, Chapter 5 of City EDS Standards and WSDOT /APWA Specification 1 -07.15 as follows: a) Erosion control plans shall be submitted to the City, approved by the City, and implemented by the contractor prior to distrubing any soil on the site. Submittal and approval of these plans shall precede any construction activity on the site. b) All permanent storage and retention /detention areas used as part of the temporary erosion control and water pollution /flood activities and conveyance systems shall be cleaned of all silts, sand, and other materials following completion of construction and the permanent facilities shall then be completed including permanent infiltration areas. 4. Horizontal and vertical controls /datum as adopted by the City shall be used, uless approved otherwise. 5. The contractor shall be fully responsible for the location and protection of all existing utilities. The contractor shall verify all utility locatons prior to construction by calling Underground Locate at 1- 800 - 424 -5555 a minimum of 48 hours prior to any excavation work. Y 6. All non — ferrous pipe and services shall be installed with continuous tracer tape installed 12" to 18" under the final ground surface. The marker tape shall be 4" wide minimum plastice non — biogradable, metal core or backing marked and color coded for the utility to be marked and which can be detected by a standard metal detector. Tape shall be Terra Tape "D" or approved equal. Inaddition to tracer tape, force mains and curved mains shall have a 14 gouge coated copper wire, wrapped around the pipe, brought up, coated shipped, and tied off at the valve stem or manhole ring. The tape and wire shall be furnished and installed by the contractor. 7. Temporary street patching may be allowed with the approval of the City Engineer. Temporary street patching shall be as described in Chapter 6 of the EDS. 8. The contractor shall provided a traffic control plan(s) for review and approval by the City Engineer in accordance with the Manual on Uniform Traffice Contral Devices (MUTCD). 9. The contractor shall have a copy of the approved plans and permits at the construction site at all times. 10. Special structures shall be installed per plans and manufacturers' recommendations. 11. All distrurbed areas shall receive temporary and permanent erosion control in the form of vegetation establishment such as grass seeding. A means shall be established to protect the permanent storm drain system prior to establishment of the permanent erosion control measures. These methods shall be included in the erosion and sediment control plans in accordance with Chapter 5 of these Standards. 12. Construction work hours shall be restricted to 7 AM to 6 PM, Monday through Friday, unless otherwise approved in writing. 13. The City Public Works Inspector shall be notified a minimum of 24 hours in advance of the need for an inspection. Every effort will be made to accommodate ;tame —day inspections if the City is notified before 8 AM. GENERAL CONDITIONS - - -- WATER 1. The City shall be given 72 hours Notice prior to scheduling a shutdown of any portion of the water system. The existing vaive must be pressure tested to City'' standards prior to connection. If an existing valve fails to pass the test, the contractor shall make the necessary r rovisionons to thest the new line prior to connection to the existing system or install a new valve. 2. The existing valves shall only be operated by City employees during construction. 3. During the construction of mains and services, the contractor shall cap, plug, or secure the ends of such lines whenever the project is shut down at the end of the day so that contaminates will not enter the lines. 4. All lines[ shall be chlorinated and tested in conformance with the standard specifications. Dechlorintation wll be done by City forces at contractor expense. 5. All water mains shall be staked for grades and alignment grade prior to starting construction. WATER PIPE SPECIFICATIONS 1. The 2" HDPE C901 shall conform to copper tube size. 2. All pfFe sha 1l 0se cvmpre551or> fittings. II JUN 1 1 2003 CITY OF POBRT TOWNSEND APPROVED NOTICE: Plans are approved excepting any errors oromissions. All work must Pass inspection in conformance with Oil applicable co*s -andrapuletronA Data: - -r, "v? .3 G 3 L- w. A7 — ,n —% > By. ANDERSON CIVIL ENGINEERS w- 9 TOWNSEND, 360) 385-0398 47th STREET WATER PLAN & PROFILE DWN BY: VIJA DATE: MAY 29, 2003 SCALE 30 SHEET 1 OF 2 2 1 REV 0 CD CDCD cu x @ w 311-1 i . s' £, r 11L 2,.a NOTE: ) INSTALL 4' TRAIL ON 51st STREET/ 20 AC /2" CRUSHED /4 "AB; SEE DETAIL SHEET 4 FS @ EDGE = 100.16 INSTALL 6" SEWER LATERAL - 5' DEPTH @ PL (TYPICAL) 3-1 Slope (TYP) — — INSTALL UITILITY TRENCH 2' WIDE/ 2" CONDUIT TYPICAL) BOTTOM EL, 96.66 FS @ EDGE = 100,76 INSTALL 6" SEWER LATERAL 5' DEPTHI @ PL (TYPICAL) 3:1 Slope (TYIP) — INSTALL UTILITY TRENCH 2' WIDE / —i 2" CONDUIT TYPICAL) BOTTOM EL.= 96.66 30 1.5' 2% .TYP 3,1 Slope (TYP) i' i STC /8 "AB 8" WATER MAIN SHOULDER (TYPICAL) PROVIDE 36" OVER CROSS SECTION 51st St - Hendricks to Sheridan NS 30 - 1 - 30 1.5' TYP SEE DETAIL SHEET 2 2 FT 4" AGG 8" WATER MAIN SHOULDER (TYPICAL) PR VIDE 36" COVER CROSS SECTION Sheridan St - 51st St to 53rd St NS ANDERSON CIVIL ENGINEERS SURVEYORS PORT TOWNSEND, WA 98368 EXP. DATE: 05 / 05 / 06 (3V 0) 385-0398 i t i III 0 I 1 -4. 4 I 3 I 2 I 1 O. TORT City of Port Townsend - Public Works Standard Detail CARSON PVC METER BOX MODELLf1419, OR EQUIVA. NT SHUT OFF WITH LOCK WING GROUND KEY 110 COMPRESSION MUELLER MODEL 825170, OR EQUIVALENT SERVICE PIPE TYPE K COPPER CORP STOP INLET IRON PIPE THREAD OUTLET FOR 110 COMPRESSION CONNECTION. EQUAL TO MUELLER #H- 15028, OR EQUAL BED WITH PEA GRAVEL x OR WASHED ROCK TO PROVIDE POSITIVE DRAIN OUT OF BOX CUSTOMER RESPONSIBILITY PROPERTYl— LINE 6'MIN 2'MAX 3/4 FEMALE FLARE 1 a I II L* COPPER STUB OUT k CHECK VALVE 5/8 "x3/4" METER SENCES SRII SERVICE SADDLE WITH SST BAND TAP SIZE AS REQUIRED ROMAC MODEL #1015, OR EQUIVALENT NOTE: 1. A PRESSURE REDUCING VALVE INSIDE A SEPARATE METER BOX IS RECOMMENDED WHERE STATIC PRESSURE IS GREATER THAN 80 PSI. 2. PRESSURE REDUCING VALVES SHALL BE INSTALLED ON CUSTOMERS PROPERTY AT LEAST 3' FROM THE WATER METER BOX. 3. SIZE OF FITTINGS AND TAP SIZE SHALL BE AS REQUIRED FOR THE TYPE OF SERVICE. 4. * INDICATES ITEMS TO BE INSTALLED BY CITY. Date: April 1997 Water Service Connection Approved Br. Single 3/4" and V Service File: EAwg_ tdlstandard\wntw Detail: W -lA t ?ORr op O s a ofPort Townsend - Public Works Department Standard Detail VALVE BOX AND EXTENSION SURFACE ATING NUT SEE NOTE 1 CREW EXTENSION NOTES: 1 VALVE OPERATING NUT EXTENSIONS ARE REQUIRED WHEN THE VALVE NUT 15 MORE THAN TWO (2) FEET BELOW FINISHED GRADE. EXTENSIONS ARE TO BE A MINIMUM OF ONE (1) FOOT LONG. ONLY ONE EXTENSION WILL BE ALLOWED PER VALVE. Date: April 1997 ApprovedBy: File. E :\engstd\standard\water Valve BOX and Extension Detail: W-4 O. TORT' tJ City of Port Townsend - Public Works Department Standard Detail 6" MIN 3/4 FEMALE X METER 2' MAX 3/4 BRASS STREET ELBOW PROPERTY 1" COPPER, NYLON BALL 3/4" LINE VALVE, MUELLER H14265, IOREQUIVALENT ' 6' BRASS NIPPLE - - — METER BOX In TYPE K COPPER 12" BRASS NIPPLE CLOSE BRASS .. • . - ... NIPPLE 1 3/4- BRASS 3/4' BULLNOSE TEE 3/4 BRASS SEE WATER SERVICE STREET ELBOW I CONNECTION - SINGLE 3/4 FEMALE X METER BACK OF WALK SET METER AND BOX TO FINISH GRADE) Date: April 1997 N I AP Water Service Connection Approved By: - Double File: E :\eng_std\standard \water Detail: W -2 O. 'PORT , J City of Port Townsend - Public Works Department Standard Detail 1 QR V^0 STANDARD C WQ%-/F MF'7ER BOX J' A4a( cF cmv Z' GALVANZED CAP MJ x a VALW.. SAME &ZE AS MAIN. BLM PLANS TARem FW 2' CALVAAV20 PIPE W. VAN= IRAN Iii fir. -_" M' M `- City of Port Townsend - Public Works Department SQUARE FEET Standard Detail 12" MIN. FT= FT= FTr FLANGED CUT —IN —TEE 2" 90'aWlf --/ mw 7NRVSrBLOCK 1 COUPLING ADAPTER AND VALW BOX PER 1 NONE STANDARD VETA" BOTH ENDS) 112 C GRAMSENOTEjJ. 1 BACIOML FOR NONE an LwanL --/ 6 4 C01,9N GRAM MH 1 4 my PELTROoma BLOCK (TYP) 10 MA?MAL Date: April 1997 "a• I DO* R.rtron h Temporary Approved By: 2" BlowoffAssembly File: E:\etlg_std\standard \water Detail' W-7B 0 5 TORT 2., City of Port Townsend - Public Works Department SQUARE FEET Standard Detail Q FT' FT= FT= FTr LIVE TAP FLANGED CUT —IN —TEE 4" 3 1 COUPLING ADAPTER 1 1 NONE 6' BOTH ENDS) 2' TYP, 2 1 1 NONE an CONCRETE THRUST 6 4 2 1 4 10" BLOCK (TYP) 10 6 3 2 6 12' 16 14 9 5 3 9 14" 22 19 12 6 3 12 16" 29 25 16 8 4 16 18" 36 31 1 20 10 5 20 20" 45 39 24 13 6 24 22' 54 47 29 15 8 29 24" 64 56 35 18 9 35 28" 87 76 48 24 12 48 2' TYP. 101 87 55 1 28 zz 55 36' 175 125 78 2' TYP. 78 42" 197 171 1 GATE VALVE z = 2 ' 107 48" 1 257 W 1 140 71 FL x Mi 140 T2 TEE FL x FL xTAPPINGVALVE FL x MJ ROMAC STAINLESS STEEL TAPPING SLEEVE VALVE AND SLEEVE SHALL BE SUPPORTED AND BACKFILLED AS SHOWN BELOW- RIGHT. CONTROLLED DENSITY BACKFILL POURED WIDTH OF TRENCH. TWO FEET PAST VALVE FLANGE UNDISTURBED STARTING 1' ABOVE THE PIPE GROUNDGATEVALVE FL x MJ 1' ABOVE PIPE -I __=- _- _ :_^ ^ ^ ^_^ TEE: APPROVED PEA GRAVEL OR SAND BEDDING MATERIAL COMPACTED —' SOLID BRICK SUPPORT NOTE: CONCRETE THRUST BLOCK 1. 11 MIL PLASTIC OR CONSTRUCTION FABRIC SHALL BE WRAPPED AROUND PIPE AND FITTINGS BEFORE THRUST BLOCK AND BACKFILL ARE POURED. 2. CONTROLLED DENSITY BACKFILL IS A PLANT MIX CONSISTING OF: 3100# SAND, 450# WATER. AND ONE SACK (94#) OF CEMENT. 3. MJ CUT IN TEES SHALL NOT BE PERMITTED. 4. SUPPORT VALVE AND SLEEVE CONTINUOUSLY THROUGH INSTALLATION. 5. ALL THRUST BLOCKS TO BE PLACED AGAINST UNDISTURBED GROUND. S. FOR ROAD REPAIR SEE STREET STANDARDS. Date: April 1997 N. I Dd. I R.W. By Connection to Approved By: Existing Main File: E:1eng_stdWwdard \water Detail: W -3 3 REVISIONS ZONE I REV DESCRIPTION DATE APPROVED O 'PORT TO City of Port Townsend - Public Works Department Standard Detail OP 0' BLIND ;- AA FLANGE 1 •T 1 °i r BLIND FLANGI C 45' BEND 22 1/2' BEND 90' BEND TEE TEE GATE VALVE [j 11 1/4' BEND CROSS THRUST BLOCK — TABLE MIN. BEARING AREA AGAINST UNDISTURBED SOIL SQUARE FEET PIPE SIZE Q FT' FT= FT= FTr FTr FT* 4" 3 1 1 1 1 NONE 6' 4 4 2 1 1 NONE an 7 6 4 2 1 4 10" 11 10 6 3 2 6 12' 16 14 9 5 3 9 14" 22 19 12 6 3 12 16" 29 25 16 8 4 16 18" 36 31 1 20 10 5 20 20" 45 39 24 13 6 24 22' 54 47 29 15 8 29 24" 64 56 35 18 9 35 28" 87 76 48 24 12 48 30" 101 87 55 1 28 14 1 55 36' 175 125 78 40 20 78 42" 197 171 1 1 01 55 27 107 48" 1 257 223 1 140 71 36 140 Date: April 1997 Approved By: File: E:kn &stftwdard \water W910PT 1. BEARING AREA OF CONCRETE THRUST - BLOCK BASED ON 200 PSI PRESSURE AND SAFE SOIL- BEARING LOAD OF 2,000 POUNDS PER SQUARE FOOT. 2. AREAS MUST BE ADJUSTED FOR OTHER PIPE SIZES, PRESSURES, AND SOIL CONDITIONS. 3. CONCRETE BLOCKING (CLASS 3000) SHALL BE CAST IN PLACE AND HAVE A MINIMUM OF 1/4 SQUARE FOOT BEARING AGAINST THE FITTING. 4. BLOCK SHALL BEAR AGAINST FITTINGS ONLY AND SHALL BE CLEAR OF JOINTS TO PERMIT TAKING UP OR DISMANTLING OF JOINT. 5. CONTRACTOR SHALL INSTALL BLOCKING ADEQUATE TO WITHSTAND FULL TEST PRESSURE UNDER ALL CONDITIONS OF SERVICE. 6. MINIMUM ROD DIAMETER SHALL BE 3/4" ASTM A -307 WITH 36KSI YIELD STRENGTH. Horizontal Thrust Blocks Detail: W -8 47th STREET WATER MAIN WATER DETAILS SIZE FSCM NO. DWG N0. REV 7 C Is' LAI It