INSPECTION MEMORANDUM ~ ~ _ ~~~
To: Suzanne W., Building & Community evelopment Department
Fr: Tom Aumock, Assistant Fire Chi
Dt: 17 September O1
Re: Piping, Valves, Fittings Inspection; acific Environmental, Inc.-Safeway Fuel Station
Ce: Pacific Environmental, Inc.
This department made site inspection on this date for the above-referenced proposal at the request of Pacific
Environmental, with Don Olin of Pacific Environmental present.
Jurisdiction is derived from Section 7902.6 of the Uniform Fire Code, 1997 Edition and this departments
"plan review memorandum" dated 20 June 2001:
1. 1. The installation of piping, valves and fittings was found consistent with the requirements of code under
Section 7902.6.3 and this department's plan review memorandum item 12.,and; use of compression fittings
[pipe-clamp type) for fuel-line piping with knurled pipe ends was noted as consistent with ANSI B31.3
standard for installation, by Pacific Environmental, and therefore is acceptable by code, and;
i 2. Piping, valves and fittings were witnessed under pressure-testing for tightness, as was conducted by
Pacific Environmental, and to be inspected by independent contractor consistent with manufacturer's
standards and Code Section 7902.6.16.2. Copies of said tests are on record with this department, and;
It is the administrative determination of this department that the subject piping, valves and fittings are hereby
approved to backfilled and covered on site by Pacific Environmental Co.
City of Pon Townsend
I81 Quincy Street Suite 30]
Port Townsend, wA 98365
Phone (360) 379-3208 Faz (360) 385.7675
•
CITY OF PORT TOWNSEND
BUILDER'S PERMIT & INSPECTION RECORD
THIS CARD MUST BE POSTED AT CONSTRUCTION SITE
Call 385-2294 for Inspection
Permit Number: BLDOl-I4IR-1 Parcel Number: 991403205 Issued: 08/31/01
Job Address: 2611 Sims Wav Zoning: CC=11 Occupancy: SS=3
Nature of Work: Construct fueling island canonv Type of Construction: Canouv: II-N
Owner: Satewav Stores, Inc. Contractor: NYD -State Contractor's
License and City Business License reuuired
GENERAL CONDITIONS APPLY -SEE LAST PAGE
SEPARATE PERMI'T'S I2EOUIRED: (see also Hermit #BLDOl-141)
ELECTRICAL (WA State Labor and Industries) (360)-417-2702
RE UIRED INSPECTIONS
APPROVED/DATE
CONTAMINATED SOIL
In the event contaminated soil is found, a!! work shall cease. The
contractor shall contact the City Building Department and request a
site visit by the Building Official. No contaminated soil may be
removed prior to the visit by the Building OJjciaJ. In the event,
contaminated soil is found, a remediation plan shall be submitted for
approval to the Building Official regarding method ojdisposal,
stockpiling of contaminant and appropriate clean-tip practices. A!!
activities shall be consistent with Cily ordinances and DOE
standards for removal and disposal of contaminated soils.
TEMPORARY EROSION/SEDIMENT CONTROL
Construction dust shall be kept to a minimum to avoid impacts to
neighboring properties. If dirt and debris are tracked onto adjacent
rights-of--way, contractor shall immediately install sediment control
measures that may include installation ofa construction drive-off
mat, tine wash and/or sweeping ofpaved surfaces. Refer to approved
plan details attached to Street and Utility Development Permit
tJSDP01-036.
DEMOLITION
Materials from demolition shall be disposed ojin areas off=site
meeting a!! qualifecations as set forth by state and local law and
other government agencies.
Ca1148 hours before you dig for utility locates
1-800-424-5555
Page 1 of 3
Budding Permit HBLDOI.141R-1 .
REQUIRED INSPECTIONS APPROVED/DATE
FOUNDATION
Dispenser Islands
Guazd Post Details
Canopy Footings
per engineering, Sheet CS-1; 3000 psi concrete ~ /Z~ ~~ 1
required - no special inspection required per
structural engineer
Reinforcement -grade 60
per engineering, Sheet CS
Vertical Ties
Hoop Ties
Anchor Bolts
per engineering, Sheet CS-2
(4) 1 ''/4" x 24" each base plate per structural
engineer
PLUMBING
-pressure test required for gas lines
FRAMING -per engineering
-Canopy connection details, Sheets CS-I and CA-1
LIGHTING -metal halide lights prohibited; high- or
low-pressure sodium required; 250 watts maximum per
fixture
- see attached plans and lighting power allowance on
Sheet E-I
FINAL
Final - C-2 design standards compliance; contact
John McDonagh @ 379-5085
Final -Fire Department Sign-Off; see memo dated
June 20, 2001
Final -Electrical (L & I}
Plumbing
Final-Banding
Ca1148 hours before you dig for utility locates
1-500-424-5555
•
Page 2 of 3
Building Pemut #BLDOl-141 R-I
GENERAL CONDITIONS
i
1. A separate electrical permit is required for any electrical work.
2. Re-inspections are required after any corcections are complete.
3. Final Inspections and approvals are required.
4. All Building Permits expire if no progress has been made within six months or, if no
inspections have been made by the Building Department within one year. Call for at least
one inspection per year to keep your permit active.
5. Revisions require review and approval prior to making changes in the field. Contact the
Building Department at 379-3208 prior to making changes to the approved plans.
6. POST THIS PERMIT ON-SITE WITH THE APPROVED PLANS.
7. A final inspection and Certificate of Occupancy is required prior to occupancy.
Ca1148 hours before you dig for utility locates
t-800-024-5555
Page 3 of 3
Waterman & Kali Building
I81 Quvicy Street, Suite 301
Pwl Tolmeend, WA 98368
Phone: (360) 379-3208 Fez: (360) 385-7675
CITY OF PORT TOWNSEND
CONSTRUCTION PERMIT & INSPECTION RECORD
TffiS CARD MUST BE POSTED AT CONSTRUCTION SITE
Ca11385-2294 for Inspection
Permit Number: BLDO1-141 Issued: 7131/01 Parcel Number: 991403205
Job Address: 2611 Sims Wav Zoning: CC=II Type: II-N/V-N Occupancy: S-3; M
Total Occupant Load: 90 Nature of Work: Construct 2685 sg ft convenience store (refer to D1-141R-1
for fueling island canouv)
Owner: Safeway Stores. Inc. Contractor: TBD -State contractor and Citv business licenses Required
GENERAL CONDITIONS APPLY -SEE LAST PAGE ~ ~- - ~ LSS a~~ ~ ~ ~ ~
~~ta~ zl~~oz
SEPARATE PERMITS REQUIRED:
Electrical -Contact Labor & Industries @ 360-417-2702
Street & Utility Development Permit -Issued 7/27/0]
Sign Permit -contact Jean Walat @ 360-385-0644
• NOTE: All welding to be done by WABO certified welders. Credentials shall be presented
to the Building Department.
RF.f1TTTRFTI TNSPF,C'.TTnNS APPROVED/DATE
TEMPORARY EROSION & SEDIMENT CONTROL
Temporary erosion and sediment control measures shall be
installed on-site per civil plans. b7spection of sill fencing
and construction entrance required prior to concrete
inspection
FOOTINGS
~~~~ ~
~,1 L~?_ /On-
Setbacks
Forms ~/ f'~ ~(
~ ~~
~~
Reinforcement -grade 60 steel (
~
UFER
Yard Light
Footings
Forms
Vertical Steel
Horizontal Ties
Call 48 hours before you dig for utility line locates
1-800-424-5555
Page 1 of 6
Pam@ XBLD01-141
REQUIRED INSPECTIONS APPR(1VF.n/1nATF.
SLAB
Forms
Reinforcement -grade 60
Anchor Bolts - 5/8" ®9' o. c. typical.
Engineered Holdowns -per sheet BS2
Floor Drains --- - --- -- ----
PLUMBING: Barrier-Fsee Compiiance Required
D-W-V R
~~~vQ481/ll/D
h-In (,
r ~ ~ we
~Q ~~ 1,~~~
~
J
oug
/
J
Floor Drains -Trap Seal Protection 1
t r
'gr Z~/(~ ro
Water Supply ! l "~
Water Hammer Arrestors
Hose Bibbs - backflow protection required
j t7 ~' Q
Grease,Trap
Condensate Drains
Refrigeration Piping
Hot Water Heater
Seismic Restraint
PTR Valve Drain to exterior
MECHANICAL
HVAC Units
Factory Applied Nameplate
Manufacturer's Operating Instructions Attached
Unit Identified for Area Served
Access and work space for maintenance
Disconnect
Condensate Drain
MOTORS -those not part of tested equipment require
NREC compliance
NREC Temperature Zones
Thermostat Controls
Deadband Control
Setback with 7 different day types
Microprocessor controls with heat indicators
Dampers
Duct Insulation and Sealing
Ca1148 hours before you dig for utility line locates
I-800-424-5555
Page 2 of 6
RE UIRED INSPECTIONS APPROVED/DATE
Pmnil #BLD01-141
FRAMING
All engineered elements require inspection prior to cover
Bbl
d
2
d
S
"
° ,. !~ Q/J„ ,~ ~~ ~i~L~
G</urxaa' G>lL
an
sheets inclu
ing
B
-
Refer to
B 6
Walls 13
/el ~~~ l ~
Engineered Shear Walls
Roof -Engineered truss plan to be on-site at time of
Inspection
Roof Drains
Window Safety Glazing
Window U-factor - .90 or better
Doors - .60 or better
Air Seal
Roof Truss/Wall Positive Connection
Fire Blocking
Draft Stop
Weather Resistive Barrier
INSULATION
Slab -not reguired with trade-off of wall insulation
Walls - R-13 required for slab trade-off q /J/J
~a/y~O I (' [/
"1•
Roof - R-21 rigid with built-up roof ~~Zs~o/
Vapor Barrier
DRYWALL J
C QIZ,~~~J7 ~
Walls
Ceiling
~D~/Z/0/
SUSPENDED CEILING
Frame and supports/Seismic Bracing
//~~ /'~/
'
Inspect prior to ceiling file installation "/
/
• Ca1148 hours before you dig for utility line locates
I-800-424-5555
Page 3 of 6
~a~~
REnU1RF.n iNSPF.( TinNC APPR(1VFritnATTi
Pmeil#eL001-141
LIGHTING - - - -- - - --- - -- -
See approved plans and NREC Lighting Summary
Daylight zones
Exterior Lighting per NREC
Exterior Lighting per SEPA/C-II Design Standards
- High- or low-sodium lights required; metal halide
prohibited
- Fixtures @ 250 watts maximum
- contact John McDonagh @ 379-5085 for inspection
approval
PARKING
Per Sheet SA 1.3 & SA 2.1
1 Bamer Free, Van Accessible space required
LANDSCAPING
Per approved sheets SL 1.1- contact John McDonagh
@ 379-5085 for inspection
DRAINAGE
contact the Public Works Departmef¢t @ 385-7212 for
inspection
FINAL
Property address posted -min. 5"numbers
Public Works Department Sign-Off
Fire Department Sign-Off
Health Department Sign-Off
Electrical Sign-off (L & I)
Barrier Free access
Plumbing -Barrier Free Required
Mechanical
WSVIAQ
Certification letter from installer stating compliance with
fresh air requirements
Restroom wall and floor covering per UBC 807
`~
~J
Call 48 hours before you dig for utility line locates
1-800-424-5555
Page 4 of 6
Prneit #aLD01-14I
FINAL (continued)
Door panic hardware Main exit may have key locking
device with sign at exit: "THIS DOOR TO REMAIN
UNLOCKED DURING BUSINESS HOURS"
with 1" high letters on contrasting background
Exit Signage
Exit Illumination
Final Planning Department - C-II Design Standards
compliance required; contact.7ohnMcDonagh @ 379-
5085 for inspection
Final -Building
GENERAL CONDITIONS
1. Contractors working on this project are required to have a Labor & Industries contractor's re¢istration
• number and a City business license. Failure to provide proof of this documentation prior to work may
result in job shut down while this is accomplished.
2. Temporary erosion and sediment control (TESC) measures shall be installed on-site and inspected prior
to beginning construction; call 385-2294, press 3. Measures shall include installation of silt fencing and
graveled construction entrance (see attached details). Adjacent rights-of--way shall be kept free of dirt
debris. Soils exposed during construction shall be temporarily stabilized with mulching, plastic sheeting,
etc. Soils shall be permanently stabilized with seeding, plantings, sodding, etc. once construction is
complete. Applicant is responsible for protection of adjacent properties.
3. All elements of engineering including nailing, holdowns, sheathing, and alternate braced wall panels
(ABWP) require inspection prior to cover.
4. Owner or owner's agent shall review and oversee correction of any and all deficiencies noted by required
inspections.
5. Re-inspection is required after inspection report corrections are completed.
6. The Building Department is unable to pass final inspection on your project until Public Works
requirements have been completed and inspected. For Public Works inspection ca11385-2294, press 3. A
• Ca1148 hours before you dig for utility line locates
I-800-424-5555
Page 5 of 6
Permit MBLDO]-141
?. Final Inspections are required prior to occupancy; A Certificate of Occupancy is required fora non-
residential project.
8. All building permits expire if no progress has been made within six months, or if no inspections are done
by the Building Department within one year. Call for at least one inspection per year to keep your
building permit active.
9. Revisions require submittal & approval prior to making changes in the field. Contact the Building
Department Q 379-3208 prior to making changes to the approved plans.
10. POST THIS PERMIT ON-SITE WITH THE APPROVED PLANS.