CITY OF PORT TOWNSEND
PERMIT & INSPECTION RECORD
THIS CARD MUST BE POSTED AT CONSTRUCTION SITE
CALL 385-2626 FOR INSPECTION
**(SEE ATTACHED FIRE DEPT. MEMO DATED 10/11/00)**
•
^. Fire Department Connection
^ Vault
^ Post Indicator Valve
Waterman &. Katz Building
181 Quincy Street Suite 301
Pon Townsend, WA 98368
Phoro (3G0) 379-37A8 Fax (360) 385-7675
Permit No: BLD00-195 Issued: 10/13/00
Job Address: 919 Haines Place Zoning: M-IIA
Nature of Work: Install Automatc Fire Sprinkler System
Use of Building: Sorav Paint Booth
Owner: Townsend Bav Marine Contractor: Vikin¢ Automatic Sprinkler Co.
REQUIRED INSPECTIONS
Site Inspections (Locates)
/ndsector
Construction Ins,Qections
Date
^ Piping, Bracing, Valve Installation
^ Check valves
^ Drain and drip device between FDC and Check Valve
^ Thrust Block Installations
^ Approval for Cover (except joints-prior to flow test)
•
Inspector
Date
Page 1 of 2
Permit XBLD00.195
Ian pections & Tests
O
Public Works Department Inspection Approval (double check detector assembly
prior to installation)
Inspector Date
O
O
O
Hydrostatic Test (2 hour, 200 psi min.)
Pressurized Air Test (24-hour dry test to 40 psi)
Flush (with sieve)
Flow Test(s) (Water pressure gauge readings= Drop:_)
Fire Alarm System Interne Test, Local Waterflow Alazm Req'd. (Tamper and
Flow) ` Seconds
Pressure Reduction Valve required if static water supply pressure > 80 psi
Elevator hoistway provided. with sprinkler head(s) at bottom (sidewall) and top
of elevator hoistway with appropriate shutoff valve in accessible location, not
more than six feet off floor level
Labeling (Control Valves, Drains, etc.)
Sprinkler Box Contents (wrench, heads, etc.)
Water Motor Alarm
Fire Department Connection -final fitting to meet City of Port Townsend's
Engineering Design Standazd W-12 (attached)
Adequate heat provision for piping protection
/aspectoi
Contractor's Material & Test Certificate filed:
As-built Plans (24 x 36" maximum format) provided on-site in a formal plans
box adjacent to sprinkler riser:
As-built Plans (24 x 36" maximum format) filed:
Fire Department Final Inspection Approval
/nspectoi Date